The effect of automatic generation control (AGC) implementation on the electrical power system
DOI:
https://doi.org/10.21831/jps.v30i1.68493Keywords:
Anti Black Out, SCADA, AGCAbstract
To enhance system resilience and prevent widespread blackouts from potential disruptions, a structured scheme is needed to reduce the impact of such disturbances. One of PLN's breakthrough initiatives is the activation of Automatic Generation Control (AGC) in the Java-Madura-Bali electricity system. Since the existing Load Frequency Control (LFC) system at Tambak Lorok PLTGU has been inactive for some time, the plant was selected for AGC implementation. This system is managed automatically by the Java Control Center (JCC) Dispatcher through a SCADA control scheme. This study aims to examine the effect of AGC activation on power plant regulation by JCC Dispatchers and to compare the SCADA system performance at Tambak Lorok with that of other power plants. A quantitative method with a descriptive approach was used, relying on SCADA point-to-point testing and real-time load trials with JCC Dispatchers. The results showed that during real-time testing, the Java-Bali grid frequency remained between 50.154 Hz and 49.819 Hz. These findings confirm AGC's effectiveness and support its broader implementation as a reliable solution for maintaining frequency stability and addressing challenges posed by intermittent renewable energy sources.
References
Peraturan Menteri ESDM Republik Indonesia, Aturan Jaringan Sistem Tenaga Listrik, Jakarta: Kementrian ESDM, 2020.
P. Kundur, Power System Stability and Control, California: McGraw-Hill, Inc., 1993.
R. S. Lubis, "Penerapan Kendali Optimal pada Automatic Generation Control (AGC) Meliputi Eksitasi dalam Sistem Multi-Area," Rekayasa Elektrika, 2009.
Siemens, Power System Control Sinaut Spectrum, 1st Edition Release 4.3, 1988.
Sub Bidang Analisa dan Evaluasi Operasi Sistem, Buku Evaluasi Operasi Tahunan (EOT) Sistem Jawa Madura Bali 2021, Jakarta: PT PLN (Persero) Unit Induk Pusat Pengatur Beban, 2021.
D. Marsudi, Operasi Sistem Tenaga Listrik, Yogyakarta: Graha Ilmu, 2016.
D. Y. Istiqomah dan A. Triwiyatno, "Analisa Indeks Kekuatan Sistem untuk Penggunaan Load Frequency Control (LFC) pada Fungsi SCADA di PT PLN (Persero) P3BJB dengan Mengamati Respon Daya Generator PLTA Cirata Unit 2," Seminar Kerja Praktik, 2014.
N. Li, L. Chen, C. Zhao dan S. H. Low, "Connecting Automatic Generation Control and Economic Dispatch from an Optimization View".
A. Narvaez, "Implementation and Tuning of the Automatic Generation Control in the Energy National Control Center of Ecuador - CENACE," IEEE, 2005.
B. Panjaitan, Teknologi Sistem Pengandalian Tenaga Listrik Berbasis SCADA, Jakarta: Prenhallindo, 1999.
I. Rasyidi dan I. Robandi, "Perencanaan Sistem AGC (Automatic Generation Control) Pada Sistem Tenaga Listrik Multi Area".
E. Yawantoro, B. Suprandono dan A. Solichan, "Analisa Keandalan Sistem Tenaga Listrik Jawa Tengah dan DIY Periode Tahun 2009-2011," Media Elektrika, 2012.
Published
How to Cite
Issue
Section
License
Who Can Submit?
Any individual may submit an original manuscript for consideration for publication in Jurnal Penelitian Saintek as long as they hold the copyright to the work or are authorized by the copyright owner(s) to submit it. Authors retain initial ownership of the copyrights to their works prior to publication, except in cases where, as a condition of employment, they have agreed to transfer copyright to their employer.
User Rights
Jurnal Penelitian Saintek is an Open Access journal. Users are granted the right to read, download, copy, distribute, print, search, or link to the full texts of articles, provided they comply with the conditions of the Creative Commons Attribution-ShareAlike License 4.0 (CC BY-SA 4.0).
https://creativecommons.org/licenses/by-sa/4.0/
Author Rights
Authors retains copyrights.
Jurnal Penelitian Saintek by http://journal.uny.ac.id/index.php/saintek is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.